H2 Sensor
The H2 SENSOR detector is suitable for installation in industrial areas and ATEX zones; thanks to its explosion-proof housing, it can be installed in zone 1 and, if equipped with the dust adapter, in zone 21. The sensitive element is housed in the stainless steel head. Developed in different versions depending on size: the “head body 2” model has a diameter of 40 mm, while the “head body 3” model has a diameter of 48 mm.
A catalytic sensor is used to detect flammable substances, combining excellent linearity up to 100% LFL with fast response times. The detector has a 12-24 Vdc power supply and a standard 4-20 mA signal output on three wires. RS485 serial communication and a 1 or 3 relay card can be added as options.
The housing is made of aluminum with a total footprint of 120 x 162 x 90 mm when equipped with a 2-body head, or 120 x 184 x 90 mm when using a 3-body head. All inputs are threaded with 3/4" NPT threads. The detector can be ATEX marked as follows:
0722 II 2G Ex db IIC T5 Gb
0722 II 2GD Ex db IIC T5 Gb
Ex tb IIIC T5 T100°C Db
IP65
Or, if equipped with a dust adapter: The detector is also certified according to the international IECEx scheme and marked:
II 2G Ex db IIC T5 Gb
II 2GD Ex db IIC T5 Gb
Ex tb IIIC T5 T100°C Db
IP65
Or, if equipped with a dust adapter:
The H2 SENSOR detector has SIL2 certified hardware and SIL3 software; by creating a redundant system, the hardware also has a SIL3 safety level.
Sensor
Application Industrial areas, ATEX Zone 1 and Zone 21 (if equipped with dust adapter, optional)
Catalytic sensor
Estimated sensor life 4/5 years
Detected gases Flammable gases
Full scale 0-100% LFL
Electrical parameters
Power supply 12-24 Vdc
Signal output Analog output 4-20 mA; 1 or 3 relay card (optional); RS485 serial output (optional)
Maximum power dissipation 5.4 W
Maximum power dissipation 5.4 W
Relay contact capacity (optional card)
1.0 A at 30 Vdc
Visual indicators -
Acoustic indicators -
Hall effect sensor -
Environmental conditions
Storage temperature -40 / +85°C
Operating temperature -40 / +60°C *
Operating humidity 20 / 90% RH @40°C *
Operating pressure 80 / 120 kPa *
Air speed 6 m/s *
Response time t90 < 60 s ; t50 < 20 s *
* Values tested according to EN 60079-29-1
Housing material: die-cast aluminum with colorfast and chemically resistant epoxy paint
Head with sensing element: stainless steel
Ex d protection method: Explosion-proof housing
Ex t: Protection method using housings,
for devices intended for use in
the presence of explosive dust (if detector equipped with dust adapter, optional)
Dimensions Overall dimensions with head body 2: 120 x 162 x 90 mm
Overall dimensions with head body 3: 120 x 184 x 90 mm
Weight Weight with head body 2: 1050 g
Weight with head body 3: 1250 g
Cable entry 3 x 3/4" NPT
IP rating IP65